●Specifications of fire extinguishers: 500ml, 950ml, 2L, 3L, 6L, 9L
● Working temperature range: 5~ 55℃
● Type: water mist, capable to put out electrical fire
● Expellant gas: nitrogen (N2)
● Storage pressure: 1.2MPa(+20℃)
● Maximum working pressure: 1.4MPa(+50 ℃ )
● Minimum working pressure: 0.8MPa(5 ℃ )
● Hydrostatic test pressure: 2.1MPa
● Extinguishing agent type: S-3-AB
● Fire ratings:
500ml: 0.5A, 8B, E, 5F
950ml: 0.5A, 8B, E, 5F
2L: 1A, 55B, E
3L: 1A, 70B, E
6L: 2A, 89B, E
9L: 3A, 113B, E
Class A solid fire
Class B combustible liquid fire
Class E electrically charged substance fire