Specifications of extinguishing agent containers: 70L, 90L, 100L, 120L, 150L, 180L
● Manner of system application: total flooding
●Design working pressure of system: 2.5 MPa
● Ejection duration: ≤ 10 s
● Heptafluoropropane filling density for storage: ≤ 1120 kg/m³
●Container storeroom temperature: -10~50℃
● Protective range: ≤ 500 ㎡, ≤ 1600 m³
●System startup mode: automatic, manual
●System startup power supply: DC 24 V, 1.5 A
I Solid fire
Such as libraries, data banks, archives, software libraries, vaults, document treasuries and important medical device rooms, etc.
II Electrical fire
Such as computer rooms, communication center rooms, testing centers, electrical substations, precision instrument rooms, physiochemical labs and electrical appliance aging chambers etc.
III Liquid fire and fusible solid fire
Such as power generators, transformers, oil-immersed sinks, hydraulic oil depots and lubricant depots.