Product standard: GB 25204-2010 Automatic Tracking and Locating Jet Extinguishing Systems
Rated pressure: 0.6MPa
Rated flow: 5L/s
Jet radius: 34m
Effective radius: 30m
Monitoring radius: 40m
Installation height: 6~15m
Working voltage: AC220V
Manner of detection: infrared and ultraviolet composite detection
Manner of connection: DN50 flange
This product is mainly used for passenger transport buildings such as airport terminals, railway station waiting halls, bus terminals and docks, commercial buildings such as atriums of large malls, supermarkets, shopping centers and indoor shopping streets, rehearsal buildings such as theaters, concert halls, movie theaters, auditoriums, memorial halls and funeral homes, large industrial factory buildings and warehouses, industrial buildings where class A articles are produced and stored, exhibition buildings such as convention and exhibition centers and exhibition halls, large office buildings and business buildings, cultural centers, museums, libraries and art galleries.